Voyager Star / VOYAGER STAR P MRCR ANT ECP SR

96633249

Data Sheet

High performance, ceiling recessed LED emergency lighting luminaire, Luminaire for central emergency light supply, for single monitoring of the luminaire via Powerline in connection with the eBox System, settable emergency light level with optic. Luminaire in maintained mode. Housing: die-cast aluminium, powder coated silver grey (close to RAL 9006). Gear box for mounting in ceiling recess:. IP20_IP40, Ceiling recessed luminaire for 68 mm ceiling cut-out and ceiling thickness from 1 - 25 mm. Lens: polycarbonate. Luminaire can be installed quickly and maintained without tools. Electrical connection (230VAC) via maximum 2.5mm² cable, loop in - loop out possible. Optimum thermal management via heat sink. Maintained mode: -30°C to +30°C, non-maintained mode: -30°C to +35°C; power supply: 220-240 V AC (+/- 10%) 50-60 Hz; 176-280 V DC Suitable for recessed installation in concrete casting surround (please order separately). Complete with LEDs.. Ceiling cutout Ø68mm in ceiling thicknesses 1-25mm.

Luminaire input power: 3.6 W
Dimensions: Ø85 x 2 mm
Weight: 0.45 kg

Mode selection
  • Lamp position:STD - standard
  • Light Source:LED
  • Luminaire luminous flux*:200 lm
  • Total emergency luminous flux:200 lm
  • Luminaire efficacy*:56 lm/W
  • Ballast:1 x 89800573 DRV EM TR CPS P NO PLC 5W 2
  • Rated median useful life*: 50000 h at 25 °C
  • Luminaire input power*:3.6 W Power factor = 0.46
  • Maintenance category CIE 97:D - Enclosed IP2X
  • LED
  • CE
  • Hfree
  • IP20_IP40
  • SC2 - Protection Class 2

Photometry

Photometric configuration

CalcExpress

Use CalcExpress to quickly carry out quick online calculations of required indoor luminaire numbers for rectangular rooms. Enter the calculation parameters for your solution such as room dimensions, mounting height, height of the useful plane and required level of illuminance, and the site will instantly suggest a solution according to the light output ratio method.

Step 1: Technical data
(lm)
(m)
(m)
(%)
Step 2: Room Data
(m)
(m)
(m)
(m)
(%)
Step 3: Result
(lx)
(%)